Web-IO 4.0 Digital 2x In, 2x Relay Out
Web-Thermometer UV 2x
3.285,00 kr. (ex. VAT)
Web-IO 4.0 Digital 4x Relay Out
2.835,00 kr. (ex. VAT)
Web-IO 4.0 Digital 2x In, 2x Relay Out
WT57150
The Web-IO 4.0 Digital can control two relay changeover contacts (CO) via TCP/IP Ethernet. Two inputs allow monitoring of potential-free contacts.
2.835,00 kr. (ex. VAT)
Description
Potential-free switching, monitoring and counting ...
The Web-IO 4.0 Digital can control two relay changeover contacts (CO) via TCP/IP Ethernet. Two inputs allow monitoring of potential-free contacts . Numerous web and network services are available to report changes to the inputs and outputs – even directly in the browser. With protocols such as OPC UA , MQTT , and REST, the Web-IO is ideally suited to the world of Industry 4.0 and the Internet of Things.
Switching signals:
- 2 switching inputs:
- Control by potential-free contacts
- integrated 32-bit pulse counter
- 2 switching outputs
- potential-free contacts as changeover contacts (CO)
- Switching voltage up to 48V
(110V, 230V via coupling relay ) - Switching current max. 2A at 24V, 0.5A at 48V
Connectivity:
- Intuitive web interface for easier operation
- German or English switchable
- Switching outputs directly from the web interface
- Adapted display for smartphones
- HTTP and HTTPS
- Current Industry 4.0 protocols:
- Box-to-Box
- Alarm and reporting functions:
- Email for alarm or status report
- SNMP queries/alarm traps V1 V2 V3
- Switching your own outputs in case of alarm
- Switching the outputs of another Web-IO
- HTTP requests to control third-party devices
- Up to 30 actions can be configured
- Dynamic integration into other websites:
- Direct access to current IO states via HTTP requests , AJAX and JavaScript
- Additional software interfaces for integration into your systems/databases:
- OPC UA , OPC DA
- Modbus TCP
- Syslog, SNMP V1 V2 V3
- TCP and UDP sockets, client and server
- HTTP, HTTPS, AJAX
- FTP (data logging)
- Internal clock
- Time synchronization via time server synchronization
- Battery-buffered device clock
- Possible uses:
- Remote monitoring and fault reporting
- Cross-site switching
- Home automation, building automation
- Process monitoring and visualization
- Light, gate and barrier control
- Machine data acquisition (MDE)
- You can find further possible uses here.
Power supply:
- External supply
- screw terminal connection
- 12 - 48V DC
- PoE - Power over Ethernet
- Phantom power via data pairs
- Supply via unused wire pairs
Standards & Co.:
- Standards-compliant in both office and industrial environments:
- high immunity to interference according to EN 61000-6-2
- Low interference emission according to EN 55032:2015 + A1 Cl. B, EN 61000-3-2 & EN 61000-3-3
- 5-year warranty
Connections, displays and controls: |
||
| Digital inputs: | 2 switching inputs | |
| Control via potential-free contacts | ||
| DC auxiliary voltage for control 5V /20mA | ||
| (Auxiliary voltage also with PoE supply) | ||
| Digital outputs: | 2 relay outputs | |
| Changeover contacts (CO) | ||
| Switching voltage 24 max.2A | ||
| Switching voltage 48 max.0.5A | ||
| Voltages up to 230V can also be switched via our coupling relays |
||
| Network: | 10/100BaseT autosensing | |
| Power supply: | 12-48V DC (approx. 100mA@24V) | |
| Galvanic isolation: | Digital inputs/outputs - network: min. 1000 V | |
| Connections: | 1 x 11-way screw terminal for IOs and power supply - pluggable 1 x RJ45 for network |
|
| Show: | Network status LEDs | |
| 4 LEDs for digital states | ||
Data transfer: |
||
| Protocols: | HTTP and HTTPS | |
| TCP and UDP sockets, client and server | ||
| MQTT - Publish and Subscribe | ||
| REST | ||
| SNMP V1 V2 V3 incl. traps | ||
| SMTP email sending | ||
| OPC UA | ||
| OPC DA via OPC server | ||
| Modbus TCP | ||
| Inventory, group management | ||
| Response times: | Data and switching traffic: typically 12ms | |
Housing and other data: |
||
| Housing: | Plastic housing for DIN rail mounting, precisely fitting for sub-distribution |
|
| 90x45x56mm (lxwxh) | ||
| Protection class: | IP20 | |
| Weight: | approx. 200 g | |
| Storage temperature: | -25°C - 70°C | |
| Operating temperature: | 0°C - 60°C | |
| Permissible humidity: | 5..95% relative humidity (non-condensing) | |