Web-IO 4.0 Digital 2x In, 2x Relay Out
Web-Thermometer UV 2x
3.285,00 kr. (ex. VAT)
Web-IO 4.0 Digital 4x Relay Out
2.835,00 kr. (ex. VAT)
Web-IO 4.0 Digital 2x In, 2x Relay Out
WT57150
The Web-IO 4.0 Digital can control two relay changeover contacts (CO) via TCP/IP Ethernet. Two inputs allow monitoring of potential-free contacts.
2.835,00 kr. (ex. VAT)
Description
Potential-free switching, monitoring and counting ...
The Web-IO 4.0 Digital can control two relay changeover contacts (CO) via TCP/IP Ethernet. Two inputs allow monitoring of potential-free contacts . Numerous web and network services are available to report changes to the inputs and outputs – even directly in the browser. With protocols such as OPC UA , MQTT , and REST, the Web-IO is ideally suited to the world of Industry 4.0 and the Internet of Things.
Switching signals:
- 2 switching inputs:
- Control by potential-free contacts
- integrated 32-bit pulse counter
- 2 switching outputs
- potential-free contacts as changeover contacts (CO)
- Switching voltage up to 48V
     (110V, 230V via coupling relay ) - Switching current max. 2A at 24V, 0.5A at 48V
Connectivity:
- Intuitive web interface for easier operation
- German or English switchable
- Switching outputs directly from the web interface
- Adapted display for smartphones
- HTTP and HTTPS
- Current Industry 4.0 protocols:
- Box-to-Box
- Alarm and reporting functions:
- Email for alarm or status report
- SNMP queries/alarm traps V1 V2 V3
- Switching your own outputs in case of alarm
- Switching the outputs of another Web-IO
- HTTP requests to control third-party devices
- Up to 30 actions can be configured
- Dynamic integration into other websites:
- Direct access to current IO states via HTTP requests , AJAX and JavaScript
- Additional software interfaces for integration into your systems/databases:
- OPC UA , OPC DA
- Modbus TCP
- Syslog, SNMP V1 V2 V3
- TCP and UDP sockets, client and server
- HTTP, HTTPS, AJAX
- FTP (data logging)
- Internal clock
- Time synchronization via time server synchronization
- Battery-buffered device clock
- Possible uses:
- Remote monitoring and fault reporting
- Cross-site switching
- Home automation, building automation
- Process monitoring and visualization
- Light, gate and barrier control
- Machine data acquisition (MDE)
- You can find further possible uses here.
Power supply:
- External supply
- screw terminal connection
- 12 - 48V DC
- PoE - Power over Ethernet
- Phantom power via data pairs
- Supply via unused wire pairs
Standards & Co.:
- Standards-compliant in both office and industrial environments:
- high immunity to interference according to EN 61000-6-2
- Low interference emission according to EN 55032:2015 + A1 Cl. B, EN 61000-3-2 & EN 61000-3-3
- 5-year warranty
Connections, displays and controls: |
||
| Digital inputs: | Â | 2 switching inputs |
| Â | Â | Control via potential-free contacts |
| Â | Â | DC auxiliary voltage for control 5V /20mA |
| Â | Â | (Auxiliary voltage also with PoE supply) |
| Digital outputs: | Â | 2 relay outputs |
| Â | Â | Changeover contacts (CO) |
| Â | Â | Switching voltage 24 max.2A |
| Â | Â | Switching voltage 48 max.0.5A |
| Â | Â | Voltages up to 230V can also be switched via our coupling relays |
| Network: | Â | 10/100BaseT autosensing |
| Power supply: | Â | 12-48V DC (approx. 100mA@24V) |
| Galvanic isolation: | Â | Digital inputs/outputs - network: min. 1000 V |
| Connections: | Â | 1 x 11-way screw terminal for IOs and power supply - pluggable 1 x RJ45 for network |
| Show: | Â | Network status LEDs |
| Â | Â | 4 LEDs for digital states |
Data transfer: |
||
| Protocols: | Â | HTTP and HTTPS |
| Â | Â | TCP and UDP sockets, client and server |
| Â | Â | MQTT - Publish and Subscribe |
| Â | Â | REST |
| Â | Â | SNMP V1 V2 V3 incl. traps |
| Â | Â | SMTP email sending |
| Â | Â | OPC UA |
| Â | Â | OPC DA via OPC server |
| Â | Â | Modbus TCP |
| Â | Â | Inventory, group management |
| Response times: | Â | Data and switching traffic: typically 12ms |
Housing and other data: |
||
| Housing: | Â | Plastic housing for DIN rail mounting, precisely fitting for sub-distribution |
| Â | Â | 90x45x56mm (lxwxh) |
| Protection class: | Â | IP20 |
| Weight: | Â | approx. 200 g |
| Storage temperature: |  | -25°C - 70°C |
| Operating temperature: |  | 0°C - 60°C |
| Permissible humidity: | Â | 5..95% relative humidity (non-condensing) |
| Scope of delivery: | Â |
1 x Web-IO 4.0 Digital, 4xIn/Out |
Reviews (0)
Show only reviews in English (0)
Be the first to review “Web-IO 4.0 Digital 2x In, 2x Relay Out” Cancel reply


Reviews